Power supply

Connect the 1 or 3 phase power supply behind a 6A circuit breaker, or use an existing circuit.


🪛 Installation instructions​

For an installation with a single energy meter (known as a PAP, a primary allocation point), the following installation diagram should be implemented. The Navigator must always be installed behind a circuit breaker or residual current device of at least 6A.

Wire gauge

Use wire with a cross-section of 0.75 mm² to 2.5 mm² (stranded or solid core). The connection method is push-in with a recommended strip length of 10 mm. Ferrules can be used but are not required.

Navigator connection diagram with single meter (PAP)