Skip to main content

SAJ HS3 via Modbus RTU (RS-485)

This guide describes step by step how to connect a SAJ HS3 battery system to the Currentt Navigator via Modbus RTU over RS-485.


✅ Compatible models

Single-phase (HS3-S2 series)

ModelPower
HS3-3K–6K-S23 – 6 kW

Three-phase (HS3-T2 series)

ModelPower
HS3-3K–12K-T23 – 12 kW

🧰 Requirements

  • Currentt Navigator Pro (with RS-485 Modbus connection)
  • RS-485 cable (twisted pair, e.g. CAT5 or a suitable 2-wire cable)
  • Phillips screwdriver (for access to the communication port)

⚠️ Safety warnings

Note

Always switch off the system before making the communication connection. Set the DC switch to OFF and switch off the AC side via the distribution board. Wait at least 5 minutes for the capacitors to discharge.


1️⃣ Step 1: Switch off the system

  1. Set the DC switch on the HS3 to OFF
  2. Switch off the AC side via the distribution board (circuit breaker)
  3. Wait at least 5 minutes for the capacitors to discharge
  4. Check that the HS3 display is off

2️⃣ Step 2: Connect the RS-485 cable

The RS-485 connection is located on the communication connector of the SAJ HS3.

SAJ HS3 communication connector

  1. Remove the communication connector from the HS3
  2. Loosen the swivel nut () and remove the sealing plug () from the cable gland
  3. Lead the RS-485 cable through the cable gland
  4. Remove the terminal block () from the connector
  5. Connect the RS-485 cable to the terminal block:

Terminal block pin definition

PinSignalDescription
11RS485_A (Data+)Non-inverting (positive)
12RS485_B (Data−)Inverting (negative)
  1. Insert the terminal block back into the connector
  2. Connect the other end to the RS-485 Modbus connection on the Currentt Navigator (A to A, B to B)
  3. Tighten the swivel nut
  4. Reattach the communication connector to the HS3
Note

Ensure that the A and B connections are wired correctly. Swapping A and B will cause communication errors.

Ground connection

Connect the ground (GND) on one side only: either to the Currentt Navigator or to the device — but never on both sides. Connecting ground on both sides can cause a ground loop, leading to communication errors.


3️⃣ Step 3: Switch on the system

  1. Switch on the AC side via the distribution board
  2. Set the DC switch on the HS3 to ON
  3. Wait for the display to start up

4️⃣ Step 4: Configure communication

The communication settings are configured via the LCD display on the HS3 or via the eSolar app.

Via the LCD display

  1. Navigate on the display to System Settings
  2. Go to Communication Settings
  3. Set the following values:
SettingValue
RS-485 Address (Modbus ID)1 (default)
Baud rate9600
ProtocolModbus RTU
  1. Confirm the settings

Via the eSolar app

  1. Connect to the HS3 via WiFi or Bluetooth
  2. Go to Advanced Settings > Communication
  3. Set the Modbus address and baud rate

5️⃣ Step 5: Configuration in the Currentt Navigator

After connecting and configuring the HS3, the system must be added in the Currentt Navigator.

  1. Click the settings icon (top right of the screen)
  2. Choose Setup Wizard
  3. Follow the on-screen steps

Manual configuration

  1. Click the settings icon (top right of the screen)
  2. Go to Components
  3. Click the + button in the Batteries section
  4. Select SAJ
  5. Enter the connection details:
ParameterValue
ConnectionModbus RTU (RS-485)
Modbus address1 (default)
Baud rate9600
Data bits8
ParityNone (N / disabled)

📋 Settings summary

ParameterValue
ConnectionRS-485 (Modbus RTU)
ProtocolModbus RTU
Modbus address1 (default)
Baud rate9600
Data bits8
ParityNone (N / disabled)

🛟 Troubleshooting

ProblemPossible causeSolution
No connectionA and B swappedCheck the polarity of the RS-485 connection (pin 11 = A, pin 12 = B)
No connectionWrong Modbus addressCheck the Modbus address on the HS3 display
No connectionWrong baud rateCheck that the baud rate matches (default 9600)
No connectionCable too long or damagedUse a shorter cable or check for damage
Unreliable communicationNo terminationPlace a 120Ω termination resistor at the end of the RS-485 bus
No communicationSystem in sleep modeThe system may not communicate when there is no PV production (depending on firmware)