SAJ HS3 via Modbus TCP

This guide describes step by step how to connect a SAJ HS3 battery system to the Currentt Navigator via Modbus TCP over the local network (Ethernet).

See also: For connection via RS-485 (Modbus RTU), see the guide SAJ HS3 Modbus RTU.


✅ Compatible models

Single-phase (HS3-S2 series)

ModelPower
HS3-3K–6K-S23 – 6 kW

Three-phase (HS3-T2 series)

ModelPower
HS3-3K–12K-T23 – 12 kW

🧰 Requirements

  • Currentt Navigator (connected to the local network)
  • Ethernet cable (RJ45, CAT5/Cat6)

1️⃣ Step 1: Connect Ethernet cable

  1. Connect an Ethernet cable (RJ45) to the Ethernet port on the HS3
  2. Connect the other end to your network switch or router
  3. The HS3 automatically obtains an IP address via DHCP

2️⃣ Step 2: Check network settings

Check the network settings via the LCD display on the HS3 or via the eSolar app.

  1. Navigate on the display to System Settings > Network Settings
  2. Check the following settings:
SettingValue
DHCPEnabled (recommended)
IP address(automatically assigned via DHCP)
  1. Note the IP address assigned to the HS3

3️⃣ Step 3: Configuration in the Currentt Navigator

After connecting the HS3 to the network, the system must be added in the Currentt Navigator.

  1. Click the settings icon (top right of the screen)
  2. Choose Setup Wizard
  3. Follow the on-screen steps

Manual configuration

  1. Click the settings icon (top right of the screen)
  2. Go to Components
  3. Click the + button in the Batteries section
  4. Select SAJ
  5. Enter the connection details:
ParameterValue
ConnectionModbus TCP
IP address(IP address of the HS3)
Port502
Modbus address1 (default)

📋 Settings summary

ParameterValue
ConnectionEthernet (Modbus TCP)
ProtocolModbus TCP
IP address(dynamic or static)
Port502
Modbus address1 (default)

🛟 Troubleshooting

ProblemPossible causeSolution
No connectionWrong IP addressCheck the IP address via the HS3 display or the router
No connectionWrong portCheck that the TCP port is set to 502
No connectionHS3 not on the networkCheck that the Ethernet cable is connected and the HS3 has an IP address
No connectionDevices on different networkEnsure the Currentt Navigator and the HS3 are on the same (V)LAN
No connection after restartIP address changed (DHCP)Set a static IP address
No communicationSystem in sleep modeThe system may not communicate when there is no PV production (depending on firmware)