Peblar EV charger

The Peblar is a range of smart EV chargers. The EV charger is connected to the Currentt Navigator via Modbus TCP (Ethernet).


⚙️ How it works

The Peblar communicates via Modbus TCP (Ethernet) with the Currentt Navigator. The Navigator reads the charging data (such as charging power and charging status) and sets the maximum charging current of the EV charger. This way the charging current is continuously matched to the available capacity of the grid connection and to the current yield of the solar panels.


✅ Compatible models

ModelType
Peblar HomeFixed cable
Peblar BusinessSocket / Fixed cable

🧰 Requirements

  • Currentt Navigator (connected to the local network)
  • Network connection (Ethernet or WiFi) for the EV charger
  • Access to the web interface of the EV charger
  • Firmware 1.6 or later on the EV charger
Firmware 1.6 or later required

Modbus TCP is supported from firmware 1.6 onwards. If you have an older firmware version, check for updates first before continuing.


🪛 Installation instructions

Step 1: Connect the EV charger to the network

  1. Connect the EV charger to your network using an Ethernet cable (recommended) or via WiFi
  2. Make sure the EV charger is on the same network as the Currentt Navigator
Tip

A wired connection is more stable than WiFi and prevents communication issues caused by a weak or fluctuating signal.

Step 2: Open the web interface

You configure the settings of the EV charger via the charger's web interface.

  1. Open a browser on a device that is on the same network as the EV charger
  2. Navigate to the charge point ID of the charger, for example PBLR-XXXXXXX.local
    • The charge point ID is printed on the sticker in the charger's Quick guide
    • You can also use the IP address of the charger
  3. Log in to the web interface
WiFi hotspot of the charger

Cannot reach the web interface? The EV charger creates its own WiFi hotspot for 15 minutes after power-up. Connect to it and navigate to 172.16.0.1. Switch the power off and on again to reactivate the hotspot.

Step 3: Check the firmware

  1. Check in the web interface whether firmware updates are available
  2. Install the latest firmware; it must be at least version 1.6
Important

After installing new firmware, the EV charger restarts and the connection with the web interface is temporarily lost.

Step 4: Enable the Modbus API

  1. In the web interface, go to Settings
  2. Open Advanced
  3. Enable the Modbus API
  4. Set the Access mode to Read & write
  5. Save the settings
Read & write is required

If the access mode is set to read only, the Currentt Navigator can read the EV charger but cannot control it. Always choose Read & write.

Disable smart charging

Set the charging strategies on the EV charger itself to Default and disable smart charging. If these remain active, the EV charger and the Currentt Navigator will work against each other.

Step 5: Configuration in the Currentt Navigator

After configuring the EV charger, it must be added in the Currentt Navigator.

  1. Click the settings icon (top right of the screen)
  2. Choose Installation wizard
  3. Follow the steps on the screen

Manual configuration

  1. Click the settings icon (top right of the screen)
  2. Go to Components
  3. Click the + button in the EV chargers section
  4. Select Peblar
  5. Under Communication, enter the connection details:
ParameterValue
HostThe IP address or hostname of the EV charger, for example pblr-<number>.local
TCP port502 (default)
  1. Click Save
Hostname of the Peblar

The hostname of the Peblar is its charge point ID, in the form pblr-<number>.local. You can find this ID on the sticker in the charger's Quick guide.

Static IP address recommended

Using an IP address instead of the hostname? Then set a static IP address on the EV charger or reserve the IP address in your router (DHCP reservation). With DHCP, the address can change after a router restart, causing the connection to drop.

Same network required

The Currentt Navigator and the EV charger must be on the same network (and the same VLAN). If they are on different network segments, the Navigator cannot reach the EV charger.


📋 Settings summary

ParameterValue
ConnectionLocal network (Ethernet or WiFi)
ProtocolModbus TCP
HostIP address or pblr-<number>.local
TCP port502
Modbus address1 (default)
Firmware1.6 or later
Modbus APIEnabled
Access modeRead & write
Charging strategyDefault (smart charging off)

🛟 Troubleshooting

ProblemPossible causeSolution
No connectionModbus API not enabledEnable the Modbus API via SettingsAdvanced
No connectionFirmware older than 1.6Update the firmware of the EV charger
No connectionWrong hostCheck the charge point ID or the IP address of the EV charger
No connectionDevices on different networksMake sure the Navigator and the EV charger are on the same (V)LAN
No connectionHostname is not resolvedUse the IP address instead of pblr-<number>.local
No connection after restartIP address changed (DHCP)Set a static IP address or create a DHCP reservation in the router
Reading works, but no controlAccess mode is set to read onlySet the access mode to Read & write
EV charger does not follow the control commandsSmart charging is enabled on the EV chargerSet the charging strategy to Default and disable smart charging
Unstable connectionWeak WiFi signalConnect the EV charger using a wired Ethernet connection

📖 Manual