Enphase inverter via Modbus TCP connection

This guide describes step by step how to connect an Enphase system to the Currentt Navigator via Modbus TCP over the local network. The connection runs via the Enphase Envoy gateway (Envoy-S Metered or IQ Gateway Metered).

See also: For systems without Modbus TCP support, refer to the External meter (alternative method) guide.


✅ Compatible Envoy gateways

Modbus TCP is only supported by Envoy gateways with built-in metering (Metered models).

ModelSupportedNote
Envoy-S StandardNoUse the external meter method
Envoy-S MeteredYesActivation by Enphase Support required
IQ Gateway (standard)NoUse the external meter method
IQ Gateway MeteredYesActivation by Enphase Support required
IQ Gateway CommercialYesActivation by Enphase Support required

🧰 Requirements

  • Currentt Navigator (connected to the local network)
  • Enphase Envoy-S Metered or IQ Gateway Metered
  • Ethernet cable (CAT5 or CAT6) — if the Envoy is not yet wired to the network
  • Network access (both devices on the same LAN or routable network)
  • Serial number and site ID of the Envoy gateway (found on the device label)

1️⃣ Step 1: Have Modbus TCP activated by Enphase Support

Modbus TCP is disabled by default on all Envoy gateways and cannot be enabled by yourself. Enphase must activate this remotely.

Enphase Support contact details

Contact Enphase Support by phone:

RegionPhone number
Netherlands / Belgium+31 (0)20 880 2085
InternationalSee enphase.com/contact

What to mention to Enphase Support

Provide the following information:

  1. Serial number of the Envoy gateway
  2. Site ID (found in the Enphase Enlighten app or on the label)
  3. Request: Activation of Modbus TCP/IP on the gateway
  4. Reason: integration with an external energy management system (Currentt Navigator)
Processing time

Activation can take up to 10 business days. Plan this well in advance.

Verification

After activation, you can verify whether Modbus TCP is active by connecting with a Modbus client (e.g. from the Currentt Navigator) on port 502 of the Envoy.


2️⃣ Step 2: Connect the Envoy gateway to the network

Ensure the Envoy gateway is connected to the local network:

  1. Most Envoy gateways are already connected to the home network via WiFi
  2. For a more stable connection, the Envoy can also be connected via an Ethernet cable (if the model has an Ethernet port)
  3. Verify that the Envoy gateway and the Currentt Navigator are on the same network

3️⃣ Step 3: Determine the IP address

To communicate via Modbus TCP, you need the IP address of the Envoy gateway.

Finding the IP address

The IP address can be found in several ways:

  • Via the Enphase Enlighten app: The IP address is displayed in the system details
  • Via your router: Check the DHCP client list of your router and look for the device named "Envoy" or the serial number
  • Via a network scan: Use a network scan app to find devices on port 502

4️⃣ Step 4: Configuration in the Currentt Navigator

After Modbus TCP has been activated by Enphase, the device must be added in the Currentt Navigator. This can be done in two ways:

  1. Click the settings icon (top right of the screen)
  2. Choose Setup wizard
  3. Follow the on-screen steps

The setup wizard guides you step by step through the complete configuration process.

⚙️ Manual configuration

  1. Click the settings icon (top right of the screen)
  2. Go to Components
  3. Click the + button in the Inverters section
  4. Select Enphase
  5. Indicate which phase the inverter is connected to (L1, L2 or L3)
  6. Under Communication, select Modbus and click Network (TCP)
  7. Set the connection parameters:
ParameterValue
IP address(IP address of the Envoy gateway)
Port502
Modbus address (Device ID)1

⚠️ Limitations and considerations

Read-only

The Currentt Navigator can only read production data from the Enphase system via Modbus TCP. It is not possible to control the micro-inverters or limit power output via this connection.

Activation by Enphase required

Modbus TCP cannot be enabled by yourself. This must always be done remotely by Enphase Support. Plan the activation well in advance.

Metered models only

Only Envoy gateways with built-in metering (Metered) support Modbus TCP. Do you have a standard (non-Metered) Envoy? Use the external meter method instead.


🛟 Troubleshooting

ProblemPossible causeSolution
No connectionModbus TCP not activatedContact Enphase Support for activation
No connectionWrong IP addressCheck the IP address via your router or Enlighten app
No connectionWrong portCheck that port 502 is being used
No connectionNot on the same networkCheck that Envoy and Navigator are on the same LAN
No dataWrong Device IDCheck that the Device ID matches (default: 1)
Activation takes longEnphase processing timeActivation can take up to 10 business days

📋 Settings summary

ParameterValue
ConnectionEthernet (LAN) or WiFi
ProtocolModbus TCP
IP address(dynamic or static)
Port502
Device ID1 (default)
ActivationBy Enphase Support (by phone)
Supported modelsEnvoy-S Metered, IQ Gateway Metered, IQ Gateway Commercial