Growatt Modbus RTU (RS-485)

This guide describes step by step how to connect a Growatt inverter to the Currentt Navigator via Modbus RTU over the RS485 port (COM connector).


✅ Compatible models

Single-phase inverters

ModelPower
MIN 2500–6000TL-XH2.5 – 6 kW

Three-phase inverters

ModelPower
MOD 3000–15000TL3-XH3 – 15 kW

Single-phase hybrid inverters

ModelPower
SPH 3000–10000TL-BL-EU3 – 10 kW

Three-phase hybrid inverters

ModelPower
SPA 4000–10000TL-BL-EU4 – 10 kW

🧰 Requirements

  • Currentt Navigator Pro (with RS-485 Modbus connection)
  • RS-485 cable (twisted pair, e.g. CAT5 or a suitable 2-wire cable)
  • Phillips screwdriver (for access to the communication port)

⚠️ Safety warnings

Note

Always switch off the inverter before making the communication connection. Set the DC switch to OFF and switch off the AC side via the distribution board.


🪛 Installation instructions

Step 1: Switch off the inverter

  1. Set the DC switch on the inverter to OFF
  2. Switch off the AC side via the distribution board (circuit breaker)
  3. Wait at least 5 minutes for the capacitors to discharge
  4. Check that the inverter display is off

Step 2: Connect the RS-485 cable

The RS-485 port is located on the bottom of the Growatt inverter, near the communication ports.

  1. Remove the cover from the COM port on the bottom of the inverter
  2. Connect the RS-485 cable to the RS-485 terminals on the inverter:
TerminalSignalDescription
RS485-AData+Non-inverting (positive)
RS485-BData−Inverting (negative)
  1. Connect the other end to the RS-485 Modbus connection on the Currentt Navigator (A to A, B to B)
  2. Use a twisted pair cable for a reliable connection
  3. Replace the cover
Note

Ensure that the A and B connections are wired correctly. Swapping A and B will cause communication errors.

Ground connection

Connect the ground (GND) on one side only: either to the Currentt Navigator or to the device — but never on both sides. Connecting ground on both sides can cause a ground loop, leading to communication errors.

Step 3: Switch on the inverter

  1. Switch on the AC side via the distribution board
  2. Set the DC switch on the inverter to ON
  3. Wait for the inverter display to start up

Step 4: Configure the inverter

The communication settings are configured via the LCD display on the inverter.

  1. Press and hold the OK/Enter button until the menu opens
  2. Navigate to the settings/parameter menu and use the default password 123 to log in
  3. Set the following values:
SettingValue
COM/Modbus address1 (leave at 1 for a single inverter; adjust for multiple inverters so each inverter has a unique address)
Baud rate9600
Frame8 data bits, no parity, 1 stop bit (9600-8-N-1) (this is the Growatt default and usually not configurable)
ProtocolModbus RTU

Additional setting for SPH/SPA models:

SettingValue
RS485 modeVPP (otherwise the inverter will not accept external control)
  1. Confirm the settings
Multiple inverters

When using multiple Growatt inverters on the same RS-485 bus, each inverter must have a unique COM/Modbus address (e.g. 1, 2, 3). Set this via the display on each inverter.

Step 5: Configuration in the Currentt Navigator

After connecting the RS-485 cable and configuring the inverter, the device must be added in the Currentt Navigator.

  1. Click the settings icon (top right of the screen)
  2. Choose Setup Wizard
  3. Follow the on-screen steps

Manual configuration

  1. Click the settings icon (top right of the screen)
  2. Go to Components
  3. Click the + button in the Inverters section
  4. Select Growatt
  5. Enter the connection details:
ParameterValue
ConnectionModbus RTU (RS-485)
Modbus address1 (default)
Baud rate9600
Data bits8
ParityNone (N / disabled)

🔗 Multiple inverters (daisy-chain)

When using multiple Growatt inverters on the same RS-485 bus:

  1. Connect the inverters to each other via RS-485 (daisy-chain)
  2. Connect the first inverter to the Currentt Navigator
  3. Give each inverter a unique Modbus address (1, 2, 3, etc.)
  4. Place a 120Ω termination resistor at the end of the RS-485 bus (on the last inverter in the chain)

📋 Settings summary

ParameterValue
ConnectionRS-485 (Modbus RTU)
ProtocolModbus RTU
Modbus address1 (default)
Baud rate9600
Data bits8
ParityNone (N / disabled)

🛟 Troubleshooting

ProblemPossible causeSolution
No connectionA and B swappedCheck the polarity of the RS-485 connection
No connectionWrong Modbus addressCheck the Modbus address on the inverter display
No connectionWrong baud rateCheck that the baud rate matches (default 9600)
No connectionWrong protocolCheck that the protocol is set to Modbus RTU (not the Growatt proprietary protocol)
No connectionCable too long or damagedUse a shorter cable or check for damage
Unreliable communicationNo terminationPlace a 120Ω termination resistor at the end of the RS-485 bus
No communicationInverter in sleep modeThe inverter may not communicate when there is no PV production (depending on model and firmware)
Read-only, no controlExternal EMS not enabledEnable the External EMS mode via the inverter display