Huawei inverter via Modbus RTU (RS485) connection

This guide describes step by step how to connect a Huawei SUN2000 inverter to the Currentt Navigator via Modbus RTU over the RS485 port (COM connector).

Note

Modbus RTU via RS485 is only possible when there is no Huawei WLAN-FE Smart Dongle installed on the inverter. Is a dongle present? Use Modbus TCP instead.

See also: For connection via the local network (Ethernet), refer to the Huawei Modbus TCP guide.


✅ Compatible devices

Single-phase inverters

ModelPower
SUN2000-2KTL–6KTL-L12 – 6 kW

Three-phase inverters

ModelPower
SUN2000-3KTL–10KTL-M13 – 10 kW
SUN2000-12KTL–20KTL-M212 – 20 kW
SUN2000-12KTL–25KTL-M512 – 25 kW

🧰 Requirements

  • Currentt Navigator
  • CAT5 or CAT6 cable (UTP)
  • Huawei FusionSolar app (iOS/Android)
  • Smartphone

⚠️ Safety warnings

Note

Always turn off the inverter before disconnecting the COM connector. Set the AC and DC switches to OFF and wait at least 5 minutes to allow the capacitors to discharge.


1️⃣ Step 1: Turn off the inverter

  1. Set the AC switch to OFF
  2. Set the DC switch to OFF (if present)
  3. Wait at least 5 minutes (capacitors discharging)

Huawei SUN2000 inverter - overview

Huawei SUN2000 inverter: the COM connector is located at the bottom


2️⃣ Step 2: Disconnect the COM connector

The RS485 connection is located on the COM connector at the bottom of the inverter. The COM connector is a round, multi-pin connector.

  1. Unscrew the locking ring of the COM connector
  2. Carefully pull the connector out of the inverter

Huawei COM connector disconnection and connection

Disconnecting the COM connector, connecting the cable, and reinstalling


3️⃣ Step 3: Connect the cable

Use a standard CAT5 or CAT6 (UTP) cable. On the inverter side, cut off the RJ45 connector and strip the individual wires.

Important

Always use a twisted pair for the A and B signal lines. The twisting of the wire pair suppresses electromagnetic interference (EMI) and is essential for a reliable RS485 connection.

Pinout single-phase inverter (SUN2000-L)

The COM connector on the single-phase inverter has 8 pins:

Huawei SUN2000-L COM connector pinout

COM connector pinout SUN2000-L (single-phase): use pin 1 (RS485A) and pin 2 (RS485B)

PinFunction
1RS485A (+)
2RS485B (-)
3Not used
4Not used
5Not used
6Not used
7Not used
8Not used

Connect the cable to pin 1 (RS485A) and pin 2 (RS485B).

Pinout three-phase inverter (SUN2000-M)

The COM connector on the three-phase inverter has 16 pins:

Huawei SUN2000-M COM connector pinout

COM connector pinout SUN2000-M (three-phase): use pin 1 (RS485A) and pin 3 (RS485B)

PinFunction
1RS485A (+)
2Not used
3RS485B (-)
4Not used
5-16Not used

Connect the cable to pin 1 (RS485A) and pin 3 (RS485B).

Note

On the three-phase inverter, RS485B is on pin 3 (not pin 2 as on the single-phase). Always verify the pinout for your model.

Wiring

Wire color (T-568B)Function
BlueRS485A (+)
Blue/whiteRS485B (-)
tip

You can also use other wire pairs, as long as you use a twisted pair and are consistent on both ends. The blue/blue-white pair is the standard choice.

Connecting to the Currentt Navigator

The Currentt Navigator has an RS-485 Modbus connector with three pins: A+, B-, and G (ground).

Currentt Navigator Pro - connection overview

Currentt Navigator Pro: the RS-485 Modbus connector is located at the top right

Connect the other end of the cable to the RS-485 terminal block on the Currentt Navigator:

Wire color (T-568B)Currentt Navigator pinInverter COM pin
BlueA+RS485A (+)
Blue/whiteB-RS485B (-)
Ground connection

Connect the ground on one side only: either to the Currentt Navigator or to the inverter — but never on both sides. Connecting ground on both sides can cause a ground loop, leading to communication errors or equipment damage.


4️⃣ Step 4: Reinstall the COM connector and power on

  1. Reinstall the COM connector into the inverter
  2. Tighten the locking ring
  3. Set the DC switch to ON
  4. Set the AC switch to ON
  5. Wait for the inverter to start up (this may take a few minutes)

5️⃣ Step 5: Configure the inverter

Verify that the RS485 Modbus settings are correctly configured via the Huawei FusionSolar app.

Connect to the inverter

  1. Download the Huawei FusionSolar app on your smartphone (iOS/Android)
  2. Connect your smartphone to the inverter's WiFi hotspot
  3. Open the FusionSolar app and choose manual connection
  4. Log in as installer with the default password 00000a
Note

Turn off your smartphone's mobile data, otherwise the inverter will not be found by the app.

Password: Has the password been changed? Reset the password according to the Huawei manual. Always ask the owner's permission before resetting a password.

Check RS485 settings

Navigate in the FusionSolar app to:

Settings >> Communication configuration >> RS485_1

Verify the following settings:

SettingValue
Baud Rate9600
Protocol TypeModbus
Com Address1
Bus Frame Capture1

6️⃣ Step 6: Configuration in the Currentt Navigator

After physically connecting and configuring the inverter, the device must be added in the Currentt Navigator. This can be done in two ways:

  1. Click the settings icon (top right of the screen)
  2. Choose Setup Wizard
  3. Follow the on-screen steps

The setup wizard guides you step by step through the complete configuration process.

Important

Is there a battery connected to the inverter (e.g. LUNA2000)? Indicate this when the setup wizard asks. This question will automatically appear during the steps.

⚙️ Manual configuration

  1. Click the settings icon (top right of the screen)
  2. Go to Components
  3. Is there a battery connected to the inverter?
    • Yes → Click the + button in the Batteries section
    • No → Click the + button in the Inverters section
  4. Select Huawei
  5. Indicate which phase the inverter is connected to (L1, L2, or L3)
  6. Under Communication, select Modbus and click RS-485
  7. Set the communication parameters:
ParameterValue
Baud Rate9600
Data Bits8
ParityNone
Stop Bits1
Modbus address (Device ID)1

🔗 Connecting multiple inverters (daisy-chain)

If there are multiple Huawei inverters at the same location, you can connect them in series (daisy-chain) via RS485:

  1. Connect the first inverter to the Currentt Navigator via the COM connector (as described above)
  2. Connect the next inverter via RS485 on the same bus
  3. Give each inverter a unique Com Address (1, 2, 3, etc.)
Note

In practice, we recommend connecting no more than 10 inverters in series for reliable communication.


🔗 Bus topology

Preferably use a daisy-chain (series) topology for the RS485 bus. For short distances (< 25 meters), a star topology often works as well. Connect a maximum of 32 devices to a single RS485 bus.


🔚 Termination resistor

For an RS485 connection, a termination resistor (120 Ohm) must be present at both ends of the bus to prevent signal reflections.

Currentt Navigator

The Currentt Navigator has a built-in termination resistor that can be enabled or disabled via software. By default, it is enabled. For a direct connection between a single inverter and the Currentt Navigator, no changes are needed.

Inverter

Check the inverter manual for whether a built-in termination resistor is present and how to activate it. The termination resistor must be active on the last inverter in the chain (or the only inverter).


🛟 Troubleshooting

ProblemPossible causeSolution
No communicationSmart Dongle is installedRemove the dongle and use RS485, or use Modbus TCP
No communicationWiring A/B swappedSwap the A and B wires
No communicationProtocol not set to ModbusCheck the RS485_1 settings via the FusionSolar app
No communicationWrong Com AddressCheck that the Com Address matches in the inverter and Navigator
No communicationWrong pins (single-phase vs. three-phase)Check the pinout: single-phase = pin 1+2, three-phase = pin 1+3
Intermittent communicationPoor cable connectionCheck that wires are securely fastened in the COM connector
Intermittent communicationCable too long (>1000m)Use a shorter cable or an RS485 repeater
Timeout errorsWrong baud rateEnsure the baud rate is 9600 on both sides

📋 Settings summary

ParameterValue
Physical portCOM connector (RS485)
ProtocolModbus
Modbus address (Com Address)1 (unique per inverter)
Baud Rate9600
Data Bits8
ParityNone
Stop Bits1
Bus Frame Capture1
CableCAT5/CAT6 UTP (twisted pair)
Single-phase pinsPin 1 (RS485A) + Pin 2 (RS485B)
Three-phase pinsPin 1 (RS485A) + Pin 3 (RS485B)
Smart DongleMust NOT be installed