SMA inverter

📋 Overview

The SMA inverter is connected to the Currentt Navigator to read production data and control the system.


⚙️ How does it work?

The Currentt Navigator communicates with the SMA inverter via Modbus TCP over the local network (Ethernet). SMA uses the SunSpec Modbus protocol — an industry standard for solar equipment. The Currentt Navigator reads production data, power levels and status information, and can control the inverter's power output.


🧰 Requirements

  • Currentt Navigator (connected to the local network)
  • Ethernet cable (RJ45, CAT5/Cat6)
  • Laptop or smartphone (for accessing the inverter's web interface)

1️⃣ Step 1: Connect the inverter to the network

All current SMA inverters have a built-in Ethernet port (RJ45).

  1. Connect an Ethernet cable (RJ45) to the Ethernet port on the SMA inverter
  2. Connect the other end to your network switch or router
  3. The inverter automatically obtains an IP address via DHCP

2️⃣ Step 2: Determine the IP address

To configure the inverter, you need its IP address.

  • Via your router: Check the DHCP client list for a device with "SMA" in the name
  • Via the SMA WiFi AP: When the inverter is not connected via Ethernet, it broadcasts its own WiFi network (SSID: SMA_[serial_number]). Connect to it and navigate to 192.168.12.3

3️⃣ Step 3: Enable Modbus TCP

Modbus TCP is disabled by default on SMA inverters and must be enabled via the web interface.

  1. Open a browser and navigate to https://[IP address] of the inverter
  2. Accept the security warning (the inverter uses a self-signed certificate)
  3. Log in as Installer:
RoleDefault password
User0000
Installer1111 (may have been changed by the installer)
  1. Navigate to Device Parameters > External Communication > Modbus
  2. Set the following values:
SettingValue
Modbus TCP ServerEnabled
Port502
Unit ID3 (default for SMA)
  1. Save the settings
Modbus address calculation

SMA uses a Unit ID which defaults to 3. The Modbus address entered in the Currentt Navigator is 123 + Unit ID. With the default Unit ID of 3, the Modbus address is 126.

Note

The default installer password is 1111, but many installers change this during commissioning. Contact the installer if the password does not work.


4️⃣ Step 4: Configuration in the Currentt Navigator

After enabling Modbus TCP, the inverter must be added in the Currentt Navigator.

  1. Click the settings icon (top right of the screen)
  2. Choose Setup Wizard
  3. Follow the on-screen steps

Manual configuration

  1. Click the settings icon (top right of the screen)
  2. Go to Components
  3. Click the + button in the Inverters section
  4. Select SMA
  5. Enter the connection details:
ParameterValue
ConnectionModbus TCP
IP address(IP address of the SMA inverter)
Port502
Modbus address126 (default: 123 + Unit ID 3)

📋 Settings summary

ParameterValue
ConnectionEthernet (Modbus TCP)
ProtocolSunSpec Modbus TCP
IP address(dynamic or static)
Port502
SMA Unit ID3 (default)
Modbus address126 (default: 123 + Unit ID)

🛟 Troubleshooting

ProblemPossible causeSolution
No connectionModbus TCP not enabledEnable Modbus TCP via the inverter's web interface
No connectionWrong IP addressCheck the IP address via the router or web interface
No connectionWrong portCheck that the port is set to 502
No connectionWrong Modbus addressCheck the Modbus address: 123 + Unit ID (default Unit ID 3 → Modbus address 126)
No connectionDevices on different networkEnsure the Navigator and the SMA inverter are on the same (V)LAN
No connection after restartIP address changed (DHCP)Set a static IP address
Cannot access web interfaceUnknown passwordContact the installer for the Installer password
Cannot change settingsGrid Guard code requiredSome settings require a Grid Guard code — contact SMA or the installer

✅ Compatible devices

Single-phase inverters (Sunny Boy)

ModelPower
SB 3.0-1AV-413 kW
SB 3.6-1AV-413.6 kW
SB 4.0-1AV-414 kW
SB 5.0-1AV-415 kW
SB 6.0-1AV-416 kW

Three-phase inverters (Sunny Tripower)

ModelPower
STP 3.0-3AV-403 kW
STP 4.0-3AV-404 kW
STP 5.0-3AV-405 kW
STP 6.0-3AV-406 kW
STP 8.0-3AV-408 kW
STP 10.0-3AV-4010 kW

Single-phase hybrid inverters (Sunny Boy Smart Energy)

ModelPower
SBS 3.6-103.6 kW
SBS 5.0-105 kW
SBS 6.0-106 kW

Three-phase hybrid inverters (Sunny Tripower Smart Energy)

ModelPower
STP SE 5.0-105 kW
STP SE 6.0-106 kW
STP SE 8.0-108 kW
STP SE 10.0-1010 kW